谷歌浏览器插件
订阅小程序
在清言上使用

Research on identification method of abnormal grounding circulating current in single‐core AC submarine cable

Yuxin Yang,Yongli Zhu, Jinsong Wang,Yan Li

IET Generation, Transmission & Distribution(2024)

引用 0|浏览8
暂无评分
摘要
Abstract The grounding circulation current of the sheath and armour of single‐core AC submarine cables is high during operation, which can easily cause insulation damage and faults. Traditional methods that only monitor the amplitude of grounding circulation current make it difficult to detect defects in the cables, so further research is needed on the mathematical mechanism and detection methods of grounding circulation current. A mathematical model for the capacitance and impedance coupling of a single‐core submarine cable was established, and the influence of factors such as active power, length of armour stripping section, armour resistivity, armour magnetic permeability and grounding resistance on the grounding circulation current was analysed. A method for identifying abnormal grounding circulation current of submarine cables based on the combination of amplitude and phase was proposed.
更多
查看译文
关键词
circulating current,fault location,identification method,single‐core,submarine cable
AI 理解论文
溯源树
样例
生成溯源树,研究论文发展脉络
Chat Paper
正在生成论文摘要