谷歌浏览器插件
订阅小程序
在清言上使用

Diagnosis and Analysis of Metal Expander Punching Defect of Oil-immersed Current Transformer

Nianping Yan, Yang Liu,Hua Wan,Leilei Zeng, Peng Wang, Xing Wu, Lingyue Dai

2023 IEEE 6th International Conference on Automation, Electronics and Electrical Engineering (AUTEEE)(2023)

引用 0|浏览5
暂无评分
摘要
In this paper, a 220 kV oil-immersed upright current transformer metal expander punching defect is studied. Through the routine test, diagnostic test and disintegration inspection of the current transformer, it is determined that the insulation paper of the intermediate screen is not completely dry, resulting in low-energy discharge during operation, resulting in a large amount of gas and metal expander punching. Finally, relevant measures and suggestions are put forward to prevent the occurrence of this defect.
更多
查看译文
关键词
current transformer,capacitance screen,low energy discharge
AI 理解论文
溯源树
样例
生成溯源树,研究论文发展脉络
Chat Paper
正在生成论文摘要