Chrome Extension
WeChat Mini Program
Use on ChatGLM

Estimation Method of Short-Circuit Current Contribution of Inverter-Based Resources for Symmetrical Faults

Energies(2023)

Cited 0|Views1
No score
Abstract
This paper proposes a practical approach to estimate the symmetrical short-circuit current (SCC) levels in overcurrent protection devices (OCPDs) installed on radial feeders for any penetration level of inverter-based distributed energy resources (DERs). The proposed method restores the lost phase protection coordination by estimating SCC values and changing the TMS of OCPDs accordingly. The method is validated by comparing the results with simulations on the IEEE 34-Node Test Feeder using MATLAB/Simulink, which shows an average error of 1.5% and a maximum error of 3.0%. For a 100% penetration level, the SCC variation through OCPDs installed on the main fault trunk (MFT) exceeds ± 10%, leading to compromised phase protection coordination. The SCC flowing reversely through OCPDs on lateral branches and the fault on the MFT could cause improper tripping. Higher SCC levels are estimated and measured for fault impedances equal to zero. The phase protection is restored by changing the TMS of OCPDs using the estimated values. The study proposes two phase protection schemes to accommodate inverter-based DERs injecting 1.2 pu and 2.0 pu of SCC for a 100% penetration level. This study contributes to improving the protection coordination of distribution networks with high penetration levels of DERs. The findings have practical implications for distribution system operators and planners to maintain safe and reliable operation of distribution feeders.
More
Translated text
Key words
distributed energy resources,inverter-based distributed generation,overcurrent protection coordination,short-circuit current contribution
AI Read Science
Must-Reading Tree
Example
Generate MRT to find the research sequence of this paper
Chat Paper
Summary is being generated by the instructions you defined