The Study of VFTO Distribution in the Insulation System of IOCT Used in Traction Network

ENERGIES(2022)

引用 0|浏览1
暂无评分
摘要
The FDS (Frequency-domain Dielectric Spectroscopy) of oil-immersed insulation paper, and semi-conductive paper with different moisture content, has been measured. The data measured are fitted as a function of frequency and moisture content using the amendatory Cole-Cole model utilizing the least square technique. Then, the broadband MTL model of the insulation system of IOCT (Inverted-type Oil-immersed Current Transformer) is established considering the capacitive electrodes thin layer, and the distribution parameters consider the moisture and frequency dependence. A new method for VFTO (Very Fast Transient Overvoltage) distribution calculation of insulation systems is proposed.
更多
查看译文
关键词
inverted-type oil-immersed current transformer,insulation system,very fast transient overvoltage,multiconductor transmission line,frequency-domain dielectric spectroscopy