谷歌浏览器插件
订阅小程序
在清言上使用

Calculation of noise field in main transformer room of indoor substation based on thermal-acoustic coupling

Energy(2024)

引用 0|浏览6
暂无评分
摘要
—In order to calculate the noise field distribution in the main transformer room of an indoor substation accurately, a thermal-acoustic coupling idea was introduced, and a noise field solving the algorithm based on thermal-acoustic coupling was proposed in view of the noise quality loss caused by the effect of ambient temperature changes. Firstly, the fluid-structure coupling model of the main transformer room is established, and the computational fluid dynamics method is used to calculate the flow field distribution and temperature boundary conditions under the action of the heat source; Then, extracting the rheological equation of the environmental boundary conditions in the flow field calculation, and use the difference function to couple the rheological equation to the sound grid to obtain the sound field coupling model under the condition of variable temperature; Finally, the modified parameter acoustic integral equation under the sound field coupling model is calculated based on the conventional Gauss numerical integration method, and the sound field of the main transformer room considering the effect of variable temperature is obtained. The algorithm has been successfully applied in the analysis of the noise field of Xi'an 110 kV Zhenxing Substation, and the error with the measured value is 2.083%.
更多
查看译文
关键词
Main transformer room,Noise field,Computational fluid dynamics,acoustics,Thermal-acoustic coupling
AI 理解论文
溯源树
样例
生成溯源树,研究论文发展脉络
Chat Paper
正在生成论文摘要