Zero-sequence controller requirements and comparison for a delta-CHB STATCOM under unbalanced operation

INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS(2024)

引用 0|浏览0
暂无评分
摘要
Delta-configured Cascaded H -Bridge (DCHB) topology is a suitable alternative for Static Synchronous Compensator (STATCOM) applications. However, under unbalanced voltage and/or current conditions, zero-sequence current needs to be injected to guarantee dc-link capacitor voltage balancing. The control loop of this zerosequence current is analyzed in this paper, in order to determine the requirements that the implemented controller must fulfill. Considering these requirements, appropriate transient response and stability margin indicators are defined to quantify and evaluate the performance of different controllers that could be employed -Proportional-Resonant controller (PR), PR controller with delay compensation (PRd), and Vector Proportional-Integral controller (VPI) are proposed and analyzed for this application in this paper. Based on the defined indicators, the VPI is the most appropriate among the studied control techniques. Experimental results validate the analytical model of the controllers and their performance.
更多
查看译文
关键词
Delta-connected Cascaded H-Bridge (DCHB),Intercluster power balancing,Resonant controller,Static Synchronous Compensator (STATCOM),Unbalanced operation,Voltage Source Converter (VSC),Zero-sequence current
AI 理解论文
溯源树
样例
生成溯源树,研究论文发展脉络
Chat Paper
正在生成论文摘要