Coreless fault current limiter with variable series reactor is an emerging technology for limiting the amplitude and shortening the fault duration in the power network with simple and reversible operation. The device includes two coaxial, coreless reactors with axial mobility to vary and increase the effective inductance of the network during the short circuit fault. The reactors are automatically returned back to their initial position after the fault is cleared, with minimal net inductance. This paper aims to analytically describe the electromagnetic theory and validate the functionality of the device. For this purpose, the resistance and inductance of the device are first computed at normal condition via the basic theory of engineering electromagnetics. Next, the respective electromechanical performance characteristics such as force, positional displacement of the reactors, and the effective inductance are calculated at the faulty condition. For verification purposes, analytical results are compared against the finite element model.