Fault Transient Study of a Meshed DC Grid With High-Temperature Superconducting DC Cables

IEEE Transactions on Power Delivery(2022)

引用 3|浏览6
暂无评分
摘要
This paper presents the DC fault transient study of a meshed DC grid with high-temperature superconducting (HTS) HVDC cables to integrate offshore wind power. A four-terminal meshed DC grid model with a ±100 kV DC voltage rating is developed. DC circuit breakers (DCCBs) are implemented in the DC grid to deal with DC cable faults. To conduct the fault transient study, the fault scenarios with different fault locations and protection delays are studied. The sensitivity study versus different DC fault locations reveals that the faults on the faulted cable will not cause the quenching of healthy cables. The sensitivity study considering different DC fault protection delays demonstrates that the HTS cables have a current-limiting effect and the long delay of DC fault protection does not result in large fault current and the quenching of healthy cables. Extensive simulations in PSCAD/EMTDC validate the founding.
更多
查看译文
关键词
DC fault,DC grid,DC circuit breaker,modular multilevel converter,superconducting HVDC cable,offshore wind power
AI 理解论文
溯源树
样例
生成溯源树,研究论文发展脉络
Chat Paper
正在生成论文摘要