A Near-Infrared TDLAS Online Detection Device for Dissolved Gas in Transformer Oil

Spectroscopy and Spectral Analysis(2021)

引用 1|浏览4
暂无评分
摘要
Transformer insulating oil uses paraffin (CnH2n+2) as the main chemical component. Due to electric arc, discharge, overheating, moisture, etc. , the chemical bonds are broken, and characteristic gases (methane, ethane, ethylene, acetylene, carbon dioxide, carbon monoxide) are generated during the long-term operation of the transformer. Therefore, Multi-component gas will be dissolved in transformer insulating oil, so an online detection device for multi-component gas is needed to ensure the normal operation of the transformer. According to the assembly requirements of the power industry, this paper conducts an online detection device of 6 types of fault characteristic gases based on near-infrared tunable diode laser absorption spectroscopy (TDLAS). Based on the near-infrared absorption bands of 6 types of fault characteristic gases, the device selects four near-infrared lasers at 1 580, 1 654, 1 626 and 1 530 nm respectively. It uses the time-division multiplexing technology of time-sharing scanning to achieve fast time-sharing of multi-component gases Sequentially detect and adopt wavelength modulation technology to eliminate the cross-interference of the background gas. The designed near-infrared TDALS multi-component gas detection device mainly detects methane (CH4), ethane (C2H6), ethylene (C2H4), acetylene (C2H2), carbon monoxide (CO) and carbon dioxide (CO2). The developed experimental device is verified with the traditional transformer oil dissolved gas method ( transformer oil meteorological chromatographic measurement method) , and the working condition stability test is carried out. The measurement range of acetylene concentration is 0. 5 similar to 1 000 mu.L.L (1). When the range is less than 5 mu L.L (1), the maximum measurement error is less than 0. 8 mu L.L (1). When the range is 5-1 000 mu L.L (1), the maximum error is below 6 mu L.L (1); the concentration measurement range of methane, ethane, and ethylene is 0. 5-1 000 mu L.L (1), the maximum measurement error is less than 6 ppm; The measurement ranges of CO and O-2 are 25 similar to 5 000 and 25 similar to 15 000 mu L.L (1), and their maximum measurement errors are below 2 and 20 mu L.L (1) respectively. The designed near-infrared TDALS multi-component gas detection device can be used for online detection of dissolved gases in transformer oil, and the measurement meets the requirements of online detection. It can operate stably and adapt to harsh working conditions. The successful design of this online detection device provides practical experience for on-line measurement of dissolved gases in the detection of transformer oil.
更多
查看译文
关键词
TDLAS, Near infrared spectroscopy, Fault gases detection, Multi-component gas detection
AI 理解论文
溯源树
样例
生成溯源树,研究论文发展脉络
Chat Paper
正在生成论文摘要