An Analysis of Customer Power Profile Events for Non-invasive Energy Meter Error Monitoring

2019 IEEE 10th International Workshop on Applied Measurements for Power Systems (AMPS)(2019)

引用 4|浏览2
暂无评分
摘要
In this paper, a statistical analysis of low voltage customers' load power profiles is carried out aiming to suggest a remote non-invasive energy meter error monitoring technique. The synthesized open access 1 s resolution load power profiles are used for the analysis. A detection procedure for power steps in a sampled load power profile is defined. Power steps are classified into overlapping and non-overlapping. It is shown that the probability distribution function of the differences of power step magnitudes acquired by a meter under test and a reference sum meter is sensitive to the errors of the meter despite the presence of overlapping power steps at other meters in the grid. A noninvasive error monitoring technique is found possible by acquiring, comparing and statistically processing simultaneous power steps at the energy meter under monitoring and reference sum meter.
更多
查看译文
关键词
power measurement,remote monitoring,watthour meters,time series analysis
AI 理解论文
溯源树
样例
生成溯源树,研究论文发展脉络
Chat Paper
正在生成论文摘要