A Monitoring Technique for Reversed Power Flow Detection With High PV Penetration Level

IEEE Transactions on Smart Grid(2015)

引用 90|浏览81
暂无评分
摘要
The integration of renewable energy resources (RESs) in power systems poses many research challenges. Research shows that the RES output may exceed the consumed power during the day. Consequently, the direction of the power flow on distribution lines can be reversed during some periods. As the voltage regulator is normally designed for unidirectional power flow, this may cause voltage violations on the distribution feeder. Therefore, most utilities try to set a penetration level (PL) limit for safe operation. On the other hand, time varying and unbalanced loading are the main characteristics of distribution systems. Moreover installation of intermittent and nondispatchable photovoltaic (PV) devices increases the control problems of distribution system. This paper presents an impedance-based monitoring method for detection of distribution system current behavior. It will be shown that by utilizing this monitoring technique, not only the small variation of PV PL can be easily detected, but also some fast transients such as the effect of cloud movement on PV system can be monitored. This monitoring technique employs only local measurements of bus voltages and line current to measure the apparent impedance seen at the installation point. The practical application of measured impedance as a monitoring technique shows its effectiveness for distribution system monitoring in presence of various PV PL.
更多
查看译文
关键词
Impedance,Impedance measurement,Monitoring,Current measurement,Power measurement,Reactive power,Load modeling